VLF (Very Low Frequency) Testers are suitable for testing power cables, transformers, switchgear, rotating machinery and other electrical apparatus.
VLF Advantages:1. Easiest to use Fully automatic microcontroller
2. Built-in printer
3. True sine wave output
4. Real-time display of actual output waveform
5. Ergonomic, menu guided, large backlit LCD
6. Storage of test results for later retrieval and print.
7. Over voltage and current protected
8. Variable frequency 0.1Hz, 0.05Hz, 0.02 Hz
9. Data of current, voltage and waveform directly sampled at HV side.
10. AC testing does not degrade good cable insulation
11. Harmful space charges are not injected into the cable insulation
12. No traveling waves are generated during testing
13. Rugged and reliable design less prone to failure from transients
Safety Features1. Short circuit protected.
2. Status display of all important safety functions and messages.
3. Safe, easy to use operation with emergency off and key switch lock-out.
4. Fully integrated discharge circuit to safely ground the DUT after testing.
5. Zero start interlock.
6. Zero voltage switching.
Specifications1. Input: 220 ± 10% Volts AC, 50/60 Hz, single phase.
2. Output-Voltage: 30, 40, 50, 60, 70, 80, 90KV
3. Output frequency: 0.1Hz, 0.05Hz, 0.02Hz.
4. Stability of frequency: Fluctuation < 0.5%
5. Measurement accuracy: ± 3%.
6. Positive and negative voltage peak errors: ≤ 3%.
7. Voltage waveform distortion: ≤ 5%
8. Construction: In two units: Controller and Booster...
9. Ambient conditions of use: Temperature Indoor and outdoor: -10º C to + 50º C.
10. Humidity: ≤ 85%AC testing of cables and electrical apparatus is now easier than ever!The product combines modern advanced digital variable frequency technology and micro computer control together, therefore, it can realize the full automatic voltage boost, stepdown, measurement and protection as well as the manual intervention in the process of automatic voltage boost. The full electronic design ensures the small size and light weight. The big LCD screen ensures the clear and visual display, and can display the output sinusoidal wave form. The printer outputs test reports.
ModelOutput
Voltage/Current
(Peak)LoadCapacityControlUnitBoosterPower
(W)Frequency/CapacitanceNetDim.
(cm)NetWt
(kg)NetDim.
(cm)NetWt
(kg)VLF-3030KV/29mA0.1Hz≤1.1uF
0.05Hz≤2.2uF
0.02Hz≤5.5uF28x37x22533x18x34251000VLF-4040KV/29mA0.1Hz≤1.1uF
0.05Hz≤2.2uF
0.02Hz≤5.5uF28x37x22535x20x36451200VLF-5050KV/59mA0.1Hz≤1.1uF
0.05Hz≤2.2uF
0.02Hz≤5.5uF28x37x22537x24x39451200VLF-6060KV/59mA0.1Hz≤0.5uF
0.05Hz≤1.0uF
0.02Hz≤2.5uF28x37x22533x18x34481500VLF-7070KV/59mA0.1Hz,≤0.5µF
0.05Hz,≤1.0µF
0.02Hz,≤2.5µF28x37x225
35x20x36482000VLF-8080KV/59mA0.1Hz,≤0.5µF
0.05Hz,≤1.0µF
0.02Hz,≤2.5µF28x37x22537x24x39482500VLF-90 90KV/59mA0.1Hz,≤0.5µF
0.05Hz,≤1.0µF
0.02Hz,≤2.5µF28x37x22537x24x39483000