This series of capacitor voltage transformers include the products with the type of TYO 150//'3-0.01 H (TYD161/v3-0.01 H), TYD150~13-0.02H (TYD161/v3-0.02H), TYD220~-0.00SH, TYD220~- 0.01 H, TYD330kv/110v-0.00SH, TYD330kv/115v-0.01H, TYD500kv~110v-0.00SH etc., which can be used for electric measurement and relay protection in the electric power system with a voltage of 150~500kV and frequency of 50Hz. The products are in accordance with the requirements of the standard GB 4 703 "Capacitor Voltage Transformers",GB19749 "Coupling capacitors and capacitor voltage dividers" & IEC 60044-5 "Capacitor Voltage Transformers".
TECHNICAL DATA SCHEDULE CAPACITOR VOLTAGE TRANSFORMER 330 kV CODE NO: 4132 | ITEM | DEscriptION | UNITS | REQUIRED | GUARANTEED | 1.01.1Type--Capacitive1.2
1.3Model no
Country of Origin-
--
TYD330/√3-0.0044H 2.02.1Voltage2.1.1Rated voltagekV3303302.1.2Rated voltage classKV3623622.2Rated frequencyHz50502.3Network neutral grounding-EffectiveEffective2.4Rated voltage factor for 30 s-1,51.52.5Rated lightning impulse withstandkV117511752.6Chopped lighting impulse withstand (3 ms)kV129012902.7Switching impulse withstand (wet)kV9509502.8Power frequency withstand voltage (1 min)kV4504502.9Creepage distancemm/kV31312.10Max. radio interference voltage at 0,5 MHz per IEC 694mV250025002.11Capacitance C1 and C2pf440044002.12Series reactor
- inductance range
- resistance range
mH
ohms
0.2
-0.2
4002.13Transformation ratio- 330kV/Ö3
: 0,11kV/Ö3
: 0,11kV/Ö3
(: 0,11kV/Ö3)330kV/√3
: 0,11kV/√3
: 0,11kV/√3 2.14Transformer characteristics
- HV/LV turn ratio range
- Normal operating flux density
-
tesla
-
-
3000:1
0.5T2.15Primary voltagekV330/Ö3330/Ö32.16Secondary voltageV110/Ö3110/Ö32.17Winding accuracy: - metering class-0,20,2 - protection class-3P3P - burden ( on each winding)VA50502.18Number of secondary winding-2 (3)22.19Winding conductor-CuCU2.20Circuit Diagram-To be enclosed with bidTo be enclosed with bid2.21HV Terminal connector for-TBA3.03.1Weight for operationkg-9503.2Weight for transportkg-10003.3Heightm-43703.4Shipping dimensions (H x W x D)m-800*700*26003.5Outline drawing number-To be enclosed with bidTo be enclosed with bid4.0-To be enclosed with bidTo be enclosed with bid5.0-IEC 60044-5
IEC 60694
IEC 60947-1IEC 60044-5
IEC 60694
IEC 60947-16.0-ISO -----------ISO9001 7.0-Outdoor, Substation SwitchyardOutdoor, Substation Switchyard8.0-Outdoor in substation switchyard