DC system-specific circuit breakers are used in rated insulation voltage of 1600V and a rated operating voltage of DC1500V and below, and rated operating currents of 250A and below. C ircuit breakers are mainly used for overload and short circuit protection of distributed power and protection circuits and power equipment in DC systems . U nder normal circumstances can be used as a line of infrequent conversion and DC motor infrequent start.
1.Normal conditions of use
Ambient air temperature does not exceed the upper limit of +70ºC, the lower limit of not less than -40ºC , 24-hour average does not exceed +35ºC. (Note: Circuit breakers for use in ambient air temperatures above + 70ºC or below -40ºC should be consulted with the manufacturer);
The installation site of the altitude does not exceed 2000m (2000m above the need for the corresponding derating)
The relative temperature of the atmosphere is not more than 50% at the highest temperature around +40ºC, and can be compared at a lower temperature.High relative humidity (for example, 90% at 20ºC), and the consideration of temperature change on the surface of the product dew.
2.Normal installation conditions
Installation conditions: the general should be vertical installation or horizontal installation;
Installation categories: Class III of circuit breaker main circuit, control circuit and auxiliary circuit are class II.
Pollution level: Three
3.Normal storage and transport conditions
The temperature limit is not lower than -40ºC,the upper limit does not exceed +70ºC Relative humidity (25ºC) does not exceed 95ºC;
The product should be lightly moved during transport,should not be reversed should be acoided violent collision Main technical parameters
Main technical parameters
frame level250ARated working voltageDC500V/DC1000V DC1250V/DC1500VRated working current(A)100/125/140/160
/180/200/225/250Rated insulation voltageDC160Pole number2Arcing distance≤50mmBreaking capacityIcu=Ics=15kAMechanical life200Short circuit
instantaneous setting5~10Degree of protectionIp20Standard ruleGB14048.2 IEC60947
Description of protection
Overload long delay protection
Ambient temperatureTest currentAppointment timeStarting state+50ºC±2ºC1.05In≥No actionCold state1.3In<2h actionHot state
Short-circuit transient protection
Ambient temperatureTest currentAppointment timeStarting state
+10ºC~+40ºC
4In or 8In≥200msNo action6In or 12In<200msactionDerated coefficient when ambient temperature changes
Ambient temperature40ºC45ºC50ºC55ºC60ºC65ºCDerated coefficient1In0.97In0.93In0.89In0.85In0.82In
A comparative relationship between the rated current of a circuit breaker and the cross section of a linked wire
Rated current100A125A140A160A180A200A225A250ACable intercepting area35mm²50mm²70mm²95mm²120mm²
.High altitude derated coefficient
Altitude2000m3000m4000m5000mOperating voltage derating coefficient10.90.80.7Operating current derating coefficient10.960.930.9