Model
DR-45-12DR-45-15DR-45-24OutputDC output Voltage12V15V24VVoltage tolerance±1.0%±1.0%±1.0%Rated Current3.75A3A1.9ARelated Power45w45w45wWave&Noise80mVp-p100mVp-p150mVp-pAdjustable range for DC Voltage±10%±10%±10%Set up,rise,hold up time800ms 600ms 50msInputVoltage Range85 ~ 264VAC 47-63HZ 120-370VDCInput Current1A/115VAC 0.5A/230VACEfficiency77%77%82%AC inrush currentCold start current 15A/115V 30A /230VACLeakage current<0.5mA/240VACProtectionOverloadRelated output power 105-135% start overload protectionProtection type: cutoff output, recovery after restart powerOver voltage13.8V-16.2V17.2V-20.2V27.6V-32.4VHiccup mode,recovers automatically after fault conditionEnvironmentWorking temp humidity-10~+60°C 20%~90%RHStor temp, humidity-20~+85°C 20%~90%RH Non-condensingSafetyWithstand voltageI/P-O/P:1.5KVAC 1minI/P-FG:1.5KVAC 1minO/P-FG:0.5KVAC 1minStandardSafety standardFit UL1012ReferDesign refer to GB4943,UL60950,EN60950EMC standardDesign refer to GB9254,EN55022 Class ASizesizeL99*W78*H55mmPackage0.4kg, 40 pcs/16kgNote:1.All parameters not specially mentioned are measured at 230VAC input, related load and 25 f ambient temperature.2.Wave&noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf&47uf parallel capacitor.3.Tolerance: includes set up tolerance, line regulation and load regulation.