Standard:Confirming to EN / IEC60898
Breaking capacity: 6kA
Protection: Against overload and short circuit
Rated current In: 0.5,1,2,3,4,6,10,13,16,20,25,32,40,50,63A
Rated voltage: 1pole 230/400V AC 50/60Hz
2,3,4pole 400V AC 50/60Hz
Rated insulation voltage Ui: 500V
Rated impulse withstand voltage Uimp: 6000V
Energy limiting class: 3
Ambient temperature: -5ºCto +40ºCpursuant to EN / IEC60898
Characteristic: Thermal operating limit: (1.13-1.45) x In
Magnetic operating: B: (3-5) x In
C: (5-10) x In
D: (10-20) x In
Number of poles:1P,1P+N,2P,3P,3P+N and 4P
Type of trip: Thermal / magnetic release
Type of terminal:Lug type and Pin type
Terminal capacity:16mmflexible or 25mmrigid up to 25A ratings
25mmflexible or 35mmrigid for 32A to 63A ratings
Protection degreez: IP20
Installation: Mounting on 35mm DIN rail
Width: 17.5mm per pole
CategoryOperationsOperation FrequencyRated CurrentElectrical Endurance4000240/h
120/h0.5~32
40~63Mechanical Endurance10000240/h0.5~63